Technical Papers


Honeywell SDSTM Cables

About Honeywell SDSTM

The Smart Distributed System is a bus system that streamlines the installation process by utilizing interoperation of intelligent inputs and outputs. The basic benefits are enhanced diagnostics, robust signal transmission, improved device response time, and overall improved communication between devices. The Smart Distributed System is completely open, modular, and compatible with standard networks, I/O, and many controllers. The network operates with standard industrial control computers, is easily upgradeable, and because of the innovative wiring method -- is easy to install.

3086A DeviceBus® for SDSPicture of 3086A DeviceBus for SDS

 

Features of SDS Networks

The network can support up to 126 individually addressable devices on a single 4-wire cable. The Smart Distributed System can be integrated with other control solutions by using other CAN integrated circuits or off-the-shelf interface devices. CAN (Controller Area Network) is a protocol that provides a method for both message checking and correction to ensure communication integrity and overall robustness. Using CAN based network hardware keeps costs down because of its wide availability and usage in systems such as automobile's ABS(Anti-lock Brake Sys).

While the SDS components used provide the advanced diagnostic features, non-SDS devices can also be connected to the four-wire cable for communication and power.

 

Belden Cable for SDS

The Belden cable for SDS is a two pair cable containing a data and power pair under the same overall rugged jacket. Each pair is shielded with a common overall drain wire for maximum signal integrity in noisy industrial environments. The cables are designed according to the Smart Distributed System physical layer specification for conformance and compatibility.

 

Features and Benefits

 

Specifications

NEC CL2
UL AWM 2464
UL Subject 13
NEC Article 725 Power Limited Circuit Cables
CSA AWM I/II A, FT1
Shield: Individual Beldfoils with common tinned copper drain wire
Insulation: data pair -- Cellular PE, power pair -- PVC
Conductor: 19 strand Tinned copper

3087A DeviceBus® for SDSPicture of 3087A DeviceBus for SDS

 

Trade No.
UL NEC
C(UL) CEC
Type
Standard
Lengths
ft.
AWG
(stranding)
dia. Inches
Nom. DCR
Insulation
material
(color
code)
Nominal
O.D.
inches
Nom
Impedance
(ohms)
Nom.
Vel.
of
Prop.
Nominal
Capacitance
Test
Frequency
Nominal
Attenuation
3086A
NEC CL2
CSA FT1
30V 80C
AWM 2464
500
1,000
2,000
2 - #16
(19x #28)
3.6 ohm/M'
2 - #20
(19x #32)
10 ohm/M'
Power pair
PVC
(blue/brown)
Data pair
Cellular PE
(black/white)
0.398 120
data pair
76%
Data
pair
12.0 pF/ft 0.125
0.500
1.000
0.18
0.35
0.47
Medium Gray PVC jacket
3087A
NEC CL2
CSA FT1
30V 80C
AWM 2464
500
1,000
2,000
2 - #22
(19x #34)
17.5ohm/M'
2 - #22
(19x #34)
17.5 ohm/M'
Power pair
PVC
(blue/brown)
Data pair
Cellular PE
(black/white)
0.290 120
data pair
76%
Data
pair
12.0 pF/ft 0.125
0.500
1.000
0.23
0.42
0.60
Medium Gray PVC jacket

Picture of a Typical System Configuration

Belden
Industrial Products

1-888-BELDEN-8